In the actual operation of power cable,
there are quite a lot of accidents caused by COLD SHRINKABLE ACCESSORIES. Generally, the most likely place for cold shrinkable accessories to fail is in
and near the middle connector and terminal head of the cable, especially the
manufacturing process of the middle connector is more complicated, so it is
relatively more likely to have potential accidents.
1. It is caused by the imperfect metal
shielding grounding of COLD SHRINKABLE ACCESSORIES. There are two points
grounded on the general cross-linked cable, and the grounding resistance value
should be less than the specified value, so as to effectively protect the
cable. If the grounding resistance value exceeds the standard a lot, a better
voltage will be induced when the cable and connector receive electric voltage,
resulting in aging and breakdown of the insulating part.
2.
Because the installation quality of COLD SHRINKABLE ACCESSORIES is not high, it
mainly refers to that during the laying and installation of cables, the bottom
of cable trench is the auxiliary point of sand or soft soil, etc. As a result,
the cable accessories are squeezed by stones or heavy objects in the cable
trench, resulting in mechanical trauma. This kind of mechanical trauma is a
very obvious fault point of cable accessories.
3. It is caused by the poor manufacturing
quality of the intermediate connector and terminal of the COLD SHRINKABLE
ACCESSORIES. If the creepage distance of the semi-conductive layer is not
treated enough during the manufacturing process, the internal impurities, sweat
and air will be contained when the cold shrinkable cable accessories shrink.
For this reason, the impurities in the cable will be free under the action of a
strong electric field after operation, Discharge occurs. In addition, German
standard machinery pointed out that in the manufacturing process of cold
shrinkable cable accessories, if the wire crimping quality is not good, it will
lead to excessive contact resistance and heating of the connector, or
insulation aging due to excessive shrinkage, so that the insulation layer is
aged and broken down, which will also lead to cable grounding short circuit,
goods phase to phase short circuit, and will also hurt other nearby cables.
The
electric field of cable joint is a distorted electric field. At the cut-off of
wire core and shielding layer, there will be electric stress concentration. The
electric field intensity is very strong, which is the weak link of the whole
joint. Through the electric field simulation analysis, when the semiconductor
layer is too long, the semiconductor layer is too short, the semiconductor
layer has no chamfer, and the silicone grease is applied unevenly in the
transition stage between the semiconductor layer and the main insulation, the
electric field distortion intensity is 4 ~ 12 times higher than the maximum
electric field intensity at the cable joint under normal conditions, especially
when the semiconductor layer has no chamfer. When the electric field distortion
intensity reaches a certain degree, insulation partial discharge breakdown will
occur.
Therefore,
it is suggested that the cable intermediate joint must be constructed in strict
accordance with the construction quality control requirements and the
specifications of the construction drawings to prevent the cable belt defects
from being put into operation. For the cable with intermediate joint that has
operated for a certain period of time, the cable oscillation wave partial
discharge test shall be carried out to find and eliminate the cable defects in
time and ensure the reliable operation of the cable line.